
Peport Prepared for: Conservation Services Group
Report Dated: October 29, 1995
By: John Proctor, Proctor Engineering Group, Boston, MA
The primary goal is to improve the energy efficiency of residential buildings with attendant benefits to the economy, environment, consumers, and nation.
Secondary goals include;
The guidelines propose a rating scale based on a Reference Home (RH). The Rated Home will be classified by how much energy it will consume for space conditioning and water heating compared to the Reference Home. The selection of the RH characteristics is therefore critical. The Reference Home must be sufficiently better than both the new and existing housing stock to provide upward pressure on building efficiency. In other words a building that ranks "Four Stars" (the level of the RH) should be recognizable as an energy efficient building. This will help meet Principle One - Incentive to Higher Efficiency. The classification of the Rated Home relative to the RH must be sufficiently valid and accurate that lenders, consumers, and others can depend on the rating to properly inform them of how this building is likely to perform. For this reason the parameters that effect space conditioning and water consumption must be determined above some minimum level of accuracy. This will help meet Principle Two -- Ratings Actually Represent Performance.
An outgrowth of the need for validity is the question of accuracy. It is important that large differences in validity and accuracy between various components of the system cannot exist. If large differences in validity and accuracy are allowed into the system Principle Three - Maintain the Primary Goal is violated. Large inaccuracies may increase sales of individual technologies, but if the tradeoffs between technologies are made with inaccurate and invalid numbers, the primary goal will not be accomplished. The use of default assumptions must be carefully scrutinized to avoid these inaccuracies.
Two items in the Reference Home definition need correction. These are air leakage rates and distribution system efficiency.
Seasonal Air Exchange Rate
Section 437.103 Paragraph a 15 sets a seasonal air exchange rate for the Reference Home at 0.65 air changes per hour (ACH). Existing energy efficient structures already have air exchange rates of less than 0.20 (see Table A in the full report. Ordering instructions listed below)
While existing structures have measured seasonal air exchange rates of 0.20 or less, Proctor Engineering Group recommends 0.35 ACH because it is an ASHRAE consensus standard. 0.35 ACH is a reasonable value for the Reference Home (it represents the efficiency limit without some form of mechanical ventilation).
How would a Reference Home air exchange rate of .35 compare to the air exchange rates in energy efficient homes and new construction?
We recommend that Section 437.103 Paragraph (a) (15) be revised to read: "A seasonal average air leakage rate of 0.35 air changes per hour;"
This would provide a Reference Home leakage rate in the top quartile to decile of efficiency for current new construction.
Seasonal Distribution Efficiency
Section 437.103 Paragraph a 13 Table 3 sets the distribution efficiency for the Reference Home with a forced air system with ducts outside the conditioned space at .72. Current new construction (which has notoriously leaky ducts) averages .72 according to the Treidler study. Studies in California, Nevada, and Arizona have shown that distribution system efficiencies above .90 are attainable without extreme measures (See Table B in the full report. Ordering instructions are listed below.)
Proctor Engineering Group recommends that the seasonal distribution efficiency for the Reference Home be .90 for ducts outside the conditioned space. This is still less efficient than the .95 goal set by the Association of State Energy and Technology Transfer Institutions (ASERTI) along with EPRI and GRI (ASERTI, 1992). Field measured distribution efficiencies for standard leaky duct construction show distribution efficiencies as high as .82. Easily achievable levels of duct tightness have shown efficiencies above .90.
We recommend that Section 437.103 Paragraph (a) (13) Table 3 be revised to show: .90 distribution efficiency for heating and cooling with ducts outside the conditioned space. Basement specification should be similarly revised.
Air Leakage
The Department has invited comments on the possible range of error that can occur with estimated air leakage or with diagnostic testing and an infiltration model. An experienced and well trained rater cannot make reasonable estimates of air leakage. Proctor Engineering Group has worked in this field since 1979 and we have worked closely with both researchers and practitioners across the United States.
We have attempted to estimate the leakage of homes before we measured that leakage, we have known some of the best practitioners in the country try to estimate leakage in advance of measuring it. We have never seen anyone capable of performing this task. We know of no study that has shown that even the most experienced person can accurately estimate the leakage rate of a single family building. On the other hand there are volumes of studies that show that using the proper diagnostic tools (a blower door) trained personnel can actually measure the leakage of a building in a short time period.
EPRI has studied the correlation between actual infiltration rates and infiltration rates modeled based on blower door testing and both the LBL and the AIM models (Palmiter and Bond, 1994) This study showed that both models tracked the base infiltration well.
Distribution Efficiency
Distribution Efficiency is at least as critical as air infiltration rates . Numerous field studies have found that many ducted distribution systems are very inefficient. . Since it is not uncommon for the distribution efficiency of a ducted system to be less than .50, this single measurement may be the most important measurement in the rating system. Many of the duct problems are hidden from view and so non destructive testing is necessary. There are duct test machines that determine the amount of duct leakage. These machines are easy to use, not very expensive and have been proven to be effective in measuring duct leakage.
We recommend that Section 437.104 Paragraph (e) be revised to read: "For existing homes, the determination of air leakage and duct leakage set forth as building elements 10 and 11 in Table 5 are determined by on-site diagnostic test data." Delete Paragraphs e1, e2, e2i, and e2ii.
Section 437.104 Paragraph e 2 i allows for a default value of 0.67 air changes to be used as the air leakage rate. This would overrate at least half of the homes.
Section 437.104 Paragraph e 2 ii allows for a yet undetermined default value to be used as the duct leakage rate. This leaves open the possibility that more than half of the homes will be overrated.
Section 437.107 a allows for a projected rating for to-be-built homes. This makes it likely that homes will actually perform below their rating.
Air Leakage
We have recommended that the raters utilize a blower door to determine the leakage of the home.
However, if the final rule allows a default air leakage that leakage rate should represent the bottom end of the housing stock. If it allows anything else it will overrate buildings and reduce the incentive for energy efficiency. Based on the known values of air leakage listed in Table A, we recommend that if a default value is used for air leakage that it be set at 2.0 ACH.
We recommend that if Section 437.104 Paragraph (e) (2) (I) is not deleted, it should be revised to read: "for air leakage 2.0 air changes per hour shall be used unless the rater has tested the air leakage of the home."
Duct Leakage We have recommended that the raters utilize a duct leakage test to determine the distribution efficiency of the home.
However, if the final rule allows a default distribution efficiency that leakage rate should represent the lower end of the housing stock. If it allows anything else it will overrate buildings and reduce the incentive for energy efficiency. Based on the known values of distribution efficiency listed in Table B, we recommend that if any default value for distribution system leakage above .45 needs to be justified by a duct leakage test.
If a higher default is used, it will create an additional and unwarranted advantage to ducted systems vs. distributed systems (e.g., heat pumps over eletctric baseboard).
We recommend that if Section 437.104 Paragraph (e) (2) (ii) is not deleted, it should be revised to read: "for ducted systems with ducts outside the conditioned space, the default distribution efficiency shall be .45 unless the rater has tested the duct leakage of the home. Projected Ratings
Since experience in California and other states has shown that houses are often built less efficient than the plans indicate, it is necessary to distinguish between a rating based on plans and defaults and a rating based on the actual home.
We recommend that Section 437.107 be changed by adding a Paragraph (c) as follows: "The projected rating must be clearly labeled as 'PROJECTED'. It also must contain a notice that the projected rating is based on a review of the plans and that no inspection has taken place to ensure that the house is built to meet the projected level of efficiency."
ASHRAE, Chapter 23 "Infiltration and Ventilation" page 23.10 Handbook of Fundamentals. American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. Atlanta, GA, 1993
Baylon, D., and J. Heller, "Methodology and Results of Blower Door Testing in Small Multi-Family Buildings". Ecotope Inc., Seattle, Washington, 1987.
Berglund, B., T. Lindvall and J. Sundell. 1984. "Buildings, Ventilation and Thermal Climate". Swedish Council for Building Research, Stockholm, Sweden.
Berkeley Solar Group 1990. "Occupancy Patterns and Energy Consumption in New California Houses (1984-1988)" California Energy Commission Sacramento
Blasnik, M., J. Proctor, T. Downey, J. Sundal and G. Peterson. 1995a. "Assessment of HVAC Installations in New Homes in Southern California Edison's Service Territory". Southern California Edison, San Dimas, CA.
Blasnik, M., J. Proctor, T. Downey, J. Sundal and G. Peterson. 1995b. "Assessment of HVAC Installations in New Homes in Nevada Power Company's Service Territory". Nevada Power Company, Electric Power Research Institute and Nevada Department of Business and Industry, State Energy Office, Las Vegas, NV. EPRI TR-105311
Byers, R., et al. 1988. "Results of Energy Use, Indoor Air Quality, and Ventilation Monitoring for RSDP Homes in Washington State". Proceedings of the 1988 ACEEE Summer Study on Energy Efficiency in Buildings, American Council for an Energy Efficient Economy, Washington, DC
Coyne, B. 1992. "A Million Miles of Ducts: Duct Sealing Update". Home Energy, pp 14-20.
Cummings, J. B., J. Tooley. 1989. "Infiltration and Pressure Differences Induced by Forced Air Systems in Florida Residences". Florida Solar Energy Center, Cape Canaveral, FL.
Dames and Moore. 1986. "50 - Home Weatherization and Indoor Air Quality Study". Wisconsin Power and Light Company, Madison, WI.
Dumont, R. S. 1987. "Improved Methods for Air Sealing Residences". Proceedings of the Fifth Annual Conference, Energy Efficient Buildings Association, Minneapolis, MN.
Grimsrud, D.T., M.H. Sherman, and R.C. Sonderegger. 1982. Calculating infiltration: Implications for a construction quality standard, 422. Proceedings of the ASHRAE-DOE Conference on the Thermal Performance of the Exterior Envelopes of Buildings II, Las Vegas.
Grot, R.A. and R.E. Clark. 1979 Air leakage characteristics and weatherization techniques for low-income housing. 178. Proceedings of the ASHRAE-DOE Conference on the Thermal Performance of the Exterior Envelopes of Buildings, Orlando, Fla.
Hewitt, D. and J. Schlegel. 1990. "Recommended Approaches to Infiltration Reduction in Electric Utility Sponsored Residential Retrofit Programs". Conservation Law Foundation, Boston Edison Company and others.
Janski, R. and M. Modera. 1993 "Sensitivity Analysis of Residential Duct System Efficiency in California", Lawrence Berkeley Laboratory Report LBL-34674 Berkeley, CA.
Johnson, R. K. 1988. "A Comparison of Two Weatherization Techniques: N.U. Seal-up vs. The Air-Sealing Specialist." Northeast Utilities, Hartford, CT.
Kolb, J. O. 1988. "Infiltration Testing of Homes Constructed to the BPA Model Conservation Standards Program". Proceedings of the 1988 ACEEE Summer Study on Energy Efficiency in Buildings". American Council for an Energy-Efficient Economy, Washington, DC
Nelson, G., R. Nevitt, N. Moyer and J. Tooley. 1993. "Measured Duct Leakage, Mechanical System Induced Pressures and Infiltration in Eight Randomly Selected New Minnesota Houses". Proceedings from the 1993 EEBA/NESEA Conference on Building Solutions, Volume II, Boston, MA.
Olson, J. R., L. Palmiter, B. Davis, M. Geffon, and T. Bond. 1993 "Field Measurements of the Heating Efficiency of Electric Forced-Air Systems in 24 Homes." Prepared for the Washington State Energy Office under Contract No. 90-05-12.
Palmiter, L. and I. Brown. 1989. The northwest residential infiltration survey, description and summary of results. Proceedings of the ASHRAE/DOE/BTECC/CIBSE Conference - Thermal Performance of the Exterior Envelope of Buildings IV, Florida, 445-57.
Palmiter, L. and T. Bond. 1994. "Measured and Modeled Infiltration: Phase II A Detailed Case Study of Three Homes. Electric Power Research Institute Report TR-102511, Palo Alto CA.
Palmiter, L. and P. W. Francisco, 1994. "Measured Efficiency of Forced-Air Distribution Systems in 24 Homes". Proceedings from the 1994 ACEEE Summer Study on Technology Research, Development and Evaluation, American Council for an Energy- Efficient Economy, Washington, DC.
Parker, D.S. 1989. "Evidence of Increased Levels of Space Heating Energy Consumption and Air Leakage Associated with Forced Air Heating Systems in Houses in the Pacific Northwest." ASHRAE Transactions , Vol. 96, Part 2. American Society of Heating, Refrigerating and Air-Conditioning Engineers, Atlanta, GA.
Parker, G.B., M. McSorley, and J. Harris. 1990. The northwest residential infiltration study: A field study of ventilation in new homes in the Pacific northwest. In Air change rate and airtightness in buildings. ASTM STP 1067 American Society for Testing and Materials, Philadelphia 93-103
Proctor, J., M. Blasnik and T. Downey. 1995a. "Southern California Edison Coachella Valley Duct and HVAC Retrofit Efficiency Improvement Pilot Project". Southern California Edison, San Dimas, CA.
Proctor, J.P. 1995b "Sensitivity of Residential Duct System Efficiency to Equipment Type, Equipment Sizing, and Climate". Conservation Services Group, Inc. Boston
Riewer, S. 1988. "Demonstrating Model Conservation Standards in Manufactured Housing". Proceedings of the 1988 ACEEE Summer Study on Energy Efficiency in Buildings, American Council for an Energy-Efficient Economy, Washington, DC
Sloss, M., T. Kelly and M. Messenger. 1990. "Consultant Report, Occupancy Patterns and Energy Consumption in New California Houses." California Energy Commission, Sacramento, CA.
Stiles, L. F. "A Fundamental Approach in the Use of Whole-House Pressurization Data for Predicting Infiltration Rates". Stockton State College, Stockton, CA.
Tridler et al.,1995 cited in "Treatment of Residential Duct Leakage in Title-24 Energy Efficiency Standards" California Energy Commission, Sacramento, CA
Also see Program Design






