Duct leakage exceeded 150 CFM 50 in 98% of the systems. It averaged 381 CFM 50 and ranged from 36 to 8130 CFM 50. Sample size 2170 homes

Duct leakage was below 150 CFM 50 in 64% of the systems after repairs. It averaged 154 CFM 50 and ranged from 1 to 900 CFM 50. Sample size 2170 homes

Duct leakage was reduced by an average of 60% on the homes treated.

Air flow measured across the indoor coil was deficient by more than 50 CFM/Ton on 44% of the systems. Sample size - 175 systems.

Systems were found to be undercharged in 22% of the sample. Thirty-three percent of units were overcharged and 45% correctly charged. Sample size - 175 systms.