Sun Power's Furnace Specifications


Sidebar to Article "Combustion Safety: How Not to Kill Your Clients"
Home Energy Magazine - Issue Dated: May/June 1995
Written by: Rob deKieffer


For a job to be considered complete, the following specifications must be met. This is not meant to be an exhaustive list.

Forced Air Standing Pilot Furnace

Gas leaks: No leaks smelled in the building or detected with gas leak solution
Venting problems: Entire venting system connected and intact (not deteriorated to the point that it is falling apart) and continuous to the outside of the building
Carbon monoxide
indicators:
No carbon built up anywhere in the system
No flame problems (ghost flames, inconsistent pattern, flames hitting heat exchanger)
No white flames
Flame interference: No flame interference when the blower comes on
Carbon Monoxide: <100 ppm in the flue. All reasonable attempts should be made to eliminate CO
Spillage: No spillage from around the draft hood or burner area using smoke test with a light
Draft/outside
temperature:
Measured draft in the vent must be higher than:
-005 in. W.C. @ >80deg.F
-.01 in. W.C. @ 30deg. to 80deg.F
-.02 in. W.C. @ <30deg.F
High limit switch: Installed and operating at 275deg.F
The furnace is not shut down by the switch during five minute test
Open return air: No open returns in furnace room, or in a location that could interfere with the combustion air for any combustion device
Water Heater
Gas leaks: No leaks detected with gas leak solution
Venting problems: Entire venting system intact
Carbon monoxide
indicators:
No carbon, no flames, no white flames
Carbon monoxide: <100 ppm in the flue
Spillage: No spillage using smoke tests with light
Draft/outside
temperature:
Measured draft in the vent must be higher than:
-.005 in. W.C. @ >80deg.F
-.01 in. W.C. @ 30deg. to 80deg.F
-.02 in. W.C. @ <30deg.F

Return to Combustion Safety Checks article