Bigger Is Not Better:
Sizing Air Conditioners Properly

Article Sidebars

Article published in Home Energy Magazine
Issue Dated: May/June 1995
Written by: John Proctor, Zinoviy Katsnelson, and Brad Wilson.


Key Cooling Terms

Sensible Cooling Load P
The heat gain of the home due to conduction, solar radiation, infiltration, appliances, people, and pets. Burning a light bulb, for example, adds only sensible load to the house. This sensible load raises the dry-bulb temperature.

Dry-bulb Temperature P
The temperature measured by a standard thermometer.

Latent Cooling Load P The net amount of moisture added to the inside air by plants, people, cooking, infiltration, and any other moisture source. The amount of moisture in the air can be calculated from a combination of dry-bulb and wet-bulb temperature measurements.

Wet-bulb Temperature P
When a wet wick is placed over a standard thermometer and air is blown across the surface, the water evaporates and cools the thermometer below the dry-bulb temperature. This cooler temperature (called the wet-bulb temperature) depends on how much moisture is in the air.

Design Conditions P
Cooling loads vary with inside and outside conditions. A set of conditions specific to the local climate are necessary to calculate the expected cooling load for a home. Inside conditions of 75 degrees F and 50% relative humidity are usually recommended as a guideline. Outside conditions are selected for the 2.5% design point.

2.5% Design
Outside summer temperatures and coincident air moisture content that will be exceeded only 2.5% of the hours from June to September. In other words, 2.5% design conditions are outdoor temperatures historically exceeded 73 out of the 2,928 hours in these summer months.

Capacity P
The capacity of an air conditioner is measured by the amount of cooling it can do when running continuously. The total capacity is the sum of the latent capacity (ability to remove moisture from the air) and sensible capacity (ability to reduce the dry-bulb temperature). Each of these capacities is rated in BTUs per hour (Btu/h). The capacity depends on the outside and inside conditions. As it gets hotter outside (or cooler inside) the capacity drops. The capacity at a standard set of conditions is often referred to as "tons of cooling."

Tons of Cooling P Air conditioner capacity is rated at 95 degrees F outside with an inside temperature of 80 degrees F and 50% relative humidity. Each ton of air conditioning is nominally 12,000 Btu/h (this comes from the fact that it takes 12,000 Btu to melt a ton of ice). While an air conditioner may be called a three ton unit, it may not produce 36,000 Btu/h in cooling. There is a wide variety of actual capacities that are called "three tons."

EER P The Energy Efficiency Ratio is the efficiency of the air conditioner. It is capacity in BTU per hour divided by the electrical input in watts. EER changes with the inside and outside conditions, falling as the temperature difference between inside and outside gets larger. EER should not be confused with SEER.

SEER P
The Seasonal Energy Efficiency Ratio is a standard method of rating air conditioners based on three tests. All three tests are run at 80 degrees F inside and 82 degrees F outside. The first test is run with humid indoor conditions, the second with dry indoor conditions, and the third with dry conditions cycling the air conditioner on for 6 minutes and off for 24 minutes. The published SEER may not represent the actual seasonal energy efficiency of an air conditioner in your climate.

Manual J
Manual J is a widely accepted method of calculating the sensible and latent cooling (and heating) loads under design conditions. It was jointly developed by the Air Conditioning Contractors of America (ACCA) and the Air-Conditioning and Refrigeration Institute (ARI).

Manual S
Manual S is the ACCA method of selecting air conditioning equipment to meet the design loads. It ensures that both the sensible capacity and the latent capacity of the selected equipment will be adequate to meet the cooling load.

Manual D
Manual D is the ACCA method for designing duct systems. Contractors often find it a laborious process and most duct systems are just installed, not designed. The amount of time necessary to design a duct system is certainly warranted in tract construction where the design is used repeatedly and for custom homes where the total cost of the home warrants a proper design. In short, designing a duct system is essential for proper equipment performance and customer comfort.



Return to "Bigger is Not Better" article or scroll for additional article sidebar information.



Calculating Cooling Loads with Manual J

Manual J is a method of calculating the cooling and heating loads for a single family residence. It calculates room by room loads for duct design purposes, and whole house loads for equipment selection purposes. It was jointly developed by the Air-Conditioning Contractors of America (ACCA) and the Air-Conditioning and Refrigeration Institute (ARI) after ACCA conducted an industry study of residential load calculations.

Manual J procedures are based on a number of sources including the ASHRAE Handbook of Fundamentals. The basic structure of Manual J is:

Heat Gain (Btu/h)J=JHTM x Area

where HTM is a Heat Transfer Multiplier (in Btu/h/square feet). Area is the area of the building component (such as a wall). The HTMs take into account orientation, shading, temperature difference, solar gain, thermal storage, diurnal temperature swing, construction, R-Values, and roof color.

Manual J is a simplified adaptation of more complex modeling, yet it does not make many of the gross assumptions that some other load calculation methods use. It estimates both the latent and sensible cooling loads (both are necessary to properly size a system).

It is the result of a process that involved a large part of the HVAC industry and is widely accepted. It is in fact the basis for many of the other methods that are used, including many of the computer programs. For the contractor it is "safe." Because contractors helped develop it, any compromises that were made were not in the direction of undersizing units.

Manual J bases the infiltration rate on floor area and Best, Average, or Poor construction, but far better models of infiltration exist based on blower door testing. Manual J also does not have a method of considering duct leakage (although the new Manual D discusses duct leakage at some length and recommends that duct leakage be eliminated, not calculated).

The existing duct leakage in homes consumes some (but usually not all) of the safety margin built into Manual J. If duct leakage were brought under control, units could be sized smaller than Manual J.

While Manual J is simplified, it is still not simple. Because of the many values and tables, it is easy to make an error when using it. In most cases, either a set of tables specific to the contractor's service area, or a computer program should be used to reduce the likelihood of errors. The Florida Solar Energy Center is developing a more simplified sizing methodology for Florida that compares favorably with Manual J results.

While individuals who have used Manual J extensively are convinced that it has a substantial oversizing margin, there are no field studies that have determined the size of that margin. For now, it is useful as a basic load calculating method as long as one understands and takes into consideration its limitations.



Return to "Bigger is Not Better" article or scroll for additional article sidebar information.



How They Size Air Conditioning Systems In Florida

To determine actual practices used by contractors to size air conditioners, researchers with the Florida Solar Energy Center recently surveyed the 450 members of the Florida Air Conditioning Contractors Association and sent surveys to a general list of 5,559 HVAC contractors.(see contact information below to obtain a copy of the survey results.)

The overall response rate was a respectable 9%. An analysis of the survey results found that the following typifies residential sizing practices in that state.

Inaccurate Sizing Methods?

When asked about contractor experiences with inaccurate sizing methods, some responses were humorous. One contractor said "listening to the builder" was the most unreliable method, while another indicated that "listening to the homeowner" was equally problematic.

The survey indicated that sizing is fairly evenly split between Manual J calculations, computer software, and estimation by floor area. Not surprisingly, each camp had strong opinions of the other methods. Many using Manual J or computerized methods regarded square footage as an inaccurate means of sizing.

Some of those using square footage mentioned that not accounting for vaulted ceilings or large expanses of glass could lead to low estimates. However, the square footage camp strongly derided Manual J and computerized methods for undersizing units. The most common reported reason for the perceived failure of Manual J or computerized methods was that customers desire lower temperatures than Manual J assumes.

Nearly 40% of the respondents indicated that they have at times purposely oversized units. Almost none purposefully undersized units. Many indicated that they round up predicted sizing by half a ton to allow for future expansion or to "reduce callbacks."

Of those who explained why they oversize, over 30% indicated a customer request - often a demand for low temperatures. By far the most commonly expressed reasons for oversizing were either to "provide more cooling" or to lower temperatures. "I oversize by 50%," indicated one contractor, "so customers will not complain."

The survey also shows that some contractors use sizing estimation values half again larger than others for sizing units, and twice as large for determining room air flow. The few respondents who did emphasize the need to size units small, were completely outnumbered by the "bigger-is-better" school.

See "How Contractors Really Size Air Conditioning Systems," by Robin K. Vieira, Danny S. Parker, Jon F. Klongerbo, Jeffrey K. Sonne, and Jo Ellen Cummings, Florida Solar Energy Center, 300 State Road 401, Cape Canaveral, FL 32920. Tel:(407)783-0300.



Return to "Bigger is Not Better" article or scroll for additional article sidebar information.



Sizing Air Conditioners: Recommendations for Contractors



Return to Bigger is Not Better article


HomeServicesExperienceReportsCompanyPeopleContact Us